Office Address: Unit 7/20 Kenworth Place, Brendale Qld 4500
Electrical Factory: Unit 3&4 24 Leonard Crescent, Brendale Qld 4500
Sheetmetal Factory: Unit 4/15 Bult Drive, Brendale QLD 4500
Telephone: (07) 3205 7388 International: +617 3205 7388
Facsimile: (07) 3205 7488 International: +617 3205 7488
Email GB Electrics

 
Home Button
Design Button
Sheetmetal Button
Powder Coating Button
Electrical Button
Photo Gallery Button
About Button
Contact Us Button
 

GB Electrics is Certified by:

Main Switchboards and motor control centres have been type tested by Testing and Certification Australia, for compliance with Australia and international standards with respect to fault capacity, Arc fault containment and temperature rise.

Click here for more information.


Australian Made, Australian Owned

 

Certification

Main switchboards and motor control centres have been type tested by Testing and Certification Australia, for compliance with Australian and international standards in respect to:

  • Fault capacity
  • Arc fault containment
  • Temperature rise

"SIGNATURE" SERIES 690 VOLT 80KA MOTOR CONTROL CENTRE

TYPE TESTING

Motor Control Centres are type tested by Testing and Certification Australia for compliance with:

  1. AS 3439.1
  2. BS EN 60439.1
  3. IEC 439.1
All type tests are ASTA certified.
Additional type testing has been carried out at The Australian Electrical Testing centre for compliance with:
  1. AS3439.1
  2. AS1939

FAULT RATING

The Motor Control Centre has been successfully type tested for a fault capacity of:
50kA
50kA
65kA
65kA
65kA
80kA
100kA
1 second Horizontal & Vertical Busbars.
3 seconds Horizontal Busbars
Conditional Short Circuit all Functional units.
1 second Horizontal & Vertical Busbars.
3 seconds Horizontal Busbars.
1 second Horizontal & Vertical Busbars.
1 second Horizontal Busbars
ASTA Certified
ASTA Certified
ASTA Certified
ASTA Certified
ASTA Certified
ASTA Certified
NATA Certified

OPERATING VOLTAGE

The motor control centre is suitable for connection to a 3 phase 50 hz supply operating at voltages of up to 690 volts.

RATED INSULATION VOLTAGE

The motor control centre has an ASTA certified rated insulation voltage of 1000 Volts.

RATED IMPULSE WITHSTAND VOLTAGE

The motor control centre has been ASTA certified for impulse withstand voltages as follows,

  1. 6kV on all functional units
  2. 16kV on horizontal and vertical busbars

OPERATING CURRENT

Minimum ratings for horizontal busbar systems are as follows,

  1. 1250 amps - 1 x 80 x 10mm Copper Busbar
  2. 1600 amps - 2 x 80 x 10mm Copper Busbars
  3. 2500 amps - 3 x 80 x 10mm Copper Busbars
  4. 3200 amps - 3 x 100 x 10mm Copper Busbars
Minimum ratings of vertical busbar systems are as follows,
  1. 460 amps - 1 x 40 x 6.3mm Copper Busbar
  2. 690 amps - 1 x 50 x 6.3mm Copper Busbar
  3. 900 amps - 1 x 80 x 6.3mm Copper Busbar
The above ratings have been proven by ASTA certified temperature rise type testing. Up to 6300amp busbar systems can be achieved by centre feeding of the horizontal busbar system.

FORM OF SEGREGATION

The motor control centre is ASTA certified as complying with Form 4 segregation it can however be supplied as Form 2, or Form 3 as an option.

DEGREE OF PROTECTION

The motor control centre is supplied as IP43, as standard however it can be supplied as IP55 as an option. These ratings have been NATA certified.

CLEARANCE AND CREEPAGE DISTANCES

The motor control centre has been ASTA certified to comply with the requirements of IEC 60439.1 for clearance and creepage distances.

EFFECTIVENESS OF PROTECTIVE CIRCUIT

The motor control centre has been ASTA certified by prospective current calibration as well as tests to verify effective connection between the exposed conductive parts of the asembly and the protective circuit.

CONSTRUCTION

The motor control is of modular construction. All sheetmetal components are manufactured from 2mm zinc annealed sheet steel.
The motor control centre has 3 variations.

  • Single sided, front connected.
  • Back to back, front connected.
  • Back connected.
There are 10 variations of tier sizing generally these consist of,
  • 360mm wide 600mm or 800mm deep.
  • 560mm wide 600mm or 800mm deep.
  • 820mm wide 600mm or 800mm deep.
  • 920mm wide 600mm or 800mm deep.
  • 1080mm wide 600mm or 800mm deep.
The standard height of the motor control centre is 2305mm. It is mounted on a 3mm x 75mm high base. The base is hot dipped galvanised.

Motor control centre modules are plug in demountable design and have a minimum size suitable for a 11 kw starter or 63 Amp feeder.

Module doors are hinged from the shelf. To open the door or to remove the module from the connected position, the functional unit switching device must first be turned to the off position.

All doors are fitted with earth provision adjacent to top hinge.

Intermediate shelves are fully modular and it is possible to remove, replace and make minor alterations to the arrangement of the motor control centre without de energising the busbar system.

In the case of single sided front connected, and back to back front connected MCC’s a vertical cable zone of 300mm (400mm optional) internal dimension runs adjacent to each tier of modules this is on the right hand side to ensure inter changeability of modules. The MCC is also provided with horizontal cable zones for interconnecting cables at the top and bottom of each tier.

Gland plates are fitted at the top and the bottom of all MCC tiers.